一般來說,施工現場用(yong)電應符合(he)下列規定(ding):
1、采用三級配電(dian)系統(即總配電(dian)柜或箱、分配電(dian)箱、開(kai)關箱)
2、采用TN-S接零保(bao)護系統;
3、采用三級(ji)漏(lou)(lou)電(dian)(dian)(dian)保(bao)護(hu)系統(tong)(即總(zong)配(pei)(pei)(pei)電(dian)(dian)(dian)箱(xiang)漏(lou)(lou)電(dian)(dian)(dian)保(bao)護(hu)器、分配(pei)(pei)(pei)箱(xiang)漏(lou)(lou)電(dian)(dian)(dian)保(bao)護(hu)器、開關箱(xiang)漏(lou)(lou)電(dian)(dian)(dian)保(bao)護(hu)器)。下面基于施工現場實例圖(tu)片,詳解三級(ji)配(pei)(pei)(pei)電(dian)(dian)(dian)箱(xiang)的(de)配(pei)(pei)(pei)置,以供大家參考學習。
1、配(pei)電房(fang)應(ying)自(zi)然(ran)通風,并(bing)應(ying)采用防止雨雪侵(qin)入和(he)動物進入的措施。配(pei)置必要的消(xiao)防器材。
2、配電房(fang)布置應(ying)合理,且操作方便,符合安全要求(qiu)。配電房(fang)應(ying)張(zhang)掛有總(zong)平面(mian)圖、總(zong)系統(tong)圖。
3、配電房的門向外開,并配鎖。
4、配電房照(zhao)明分(fen)別(bie)設置正常照(zhao)明和(he)事故照(zhao)明。
5、配電(dian)(dian)柜(ju)或配電(dian)(dian)線(xian)路停電(dian)(dian)檢(jian)修時,應(ying)懸(xuan)掛“禁止合閘,有人(ren)工(gong)作”停電(dian)(dian)標志牌(pai)。停電(dian)(dian)時必須由專人(ren)負責。張掛電(dian)(dian)工(gong)操作規程(cheng)。電(dian)(dian)柜(ju)前(qian)地面設絕緣膠。
6、配電房沿墻周邊設置接(jie)地等壓帶(dai)。
分配電箱要求(qiu):
1、分配電(dian)箱的(de)電(dian)器(qi)安(an)裝板(ban)上(shang)必須分設N線和PE線端子板(ban)。
2、分配電箱應(ying)裝設總隔(ge)離(li)開關(guan)、分路隔(ge)離(li)開關(guan),以(yi)及分路漏電保護器。
3、分配電箱不得安(an)裝插座(zuo)做電氣連接。
4、漏電保護器應裝(zhuang)設(she)在(zai)分配箱(xiang)靠(kao)近負荷的一側。
5、分配電箱(xiang)與開關箱(xiang)距離不得(de)超過(guo)30m。
6、分(fen)配電箱的漏(lou)電開(kai)關額定漏(lou)電動作電流為100mA,額定動作時間(jian)為0.1S。